您好,欢迎来到测品娱乐。
搜索
您的当前位置:首页SAES-J-200 Pressure

SAES-J-200 Pressure

来源:测品娱乐


Engineering Standard

SAES-J-200 Pressure

Instrumentation Standards Committee Members

Al-Juaib, Mohammed Khalifah, Chairman Tuin, Rienk, Vice Chairman

Al-Faer Al Sharif, Hisham Mohammed Al-Dakhil, Tareq Khalil Al-Harbi, Ahmed Saad Al-Jumah, Yousif Ahmed Al-Khalifa, Ali Hussain

Al-Qaffas, Saleh Abdal Wahab Al-Sahan, Fawaz Adnan Al-Saleem, Hesham Salem Fadley, Gary Lowell

Falkenberg, Anton Raymond Grainger, John Francis Qarni, Mahdi Ali

Trembley, Robert James Mahmood, Balal Chetia, Manoj Mathew, Vinod Ell, Steven Tal

8 October 2008

Saudi Aramco DeskTop Standards

Table of Contents

1 Scope............................................................. 2 2 Conflicts and Deviations................................. 2 3 References..................................................... 2 4 Modifications to PIP PCCPR001, Pressure Measurement Design Criteria......... 3

Previous Issue: 18 May 2008 Next Planned Update: 18 May 2013

Primary contact: Flanders, Patrick Scott on 966-3-87413

Copyright©Saudi Aramco 2008. All rights reserved.

Page 1 of 6

Document Responsibility: Instrumentation Issue Date: 8 October 2008

Next Planned Update: 18 May 2013

SAES-J-200

Pressure

1 Scope

This standard prescribes the minimum mandatory requirements governing the design and installation of pressure and differential pressure (D/P) instruments.

The requirements of this standard are in addition to and supplement the requirements of the Process Industry Practice PIP PCCPR001, \"Pressure Measurement Criteria\" referenced in Section 3 of this standard. 2

Conflicts and Deviations 2.1

Any conflicts between this Standard and other applicable Saudi Aramco

Engineering Standards (SAESs), Materials System Specifications (SAMSSs), Standard Drawings (SASDs), or industry standards, codes, and forms shall be resolved in writing by the Company or Buyer Representative through the

Manager, Process & Control Systems Department of Saudi Aramco, Dhahran. Direct all requests to deviate from this standard in writing to the Company or Buyer Representative, who shall follow internal company procedure SAEP-302 and forward such requests to the Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.

2.2

3 References

The selection of material and equipment, and the design, construction, maintenance, and repair of equipment and facilities covered by this standard shall comply with the latest edition of the references listed below, unless otherwise noted. 3.1

Saudi Aramco References

Saudi Aramco Engineering Procedure

SAEP-302 Instructions for Obtaining a Waiver of a

Mandatory Saudi Aramco Engineering Requirement Saudi Aramco Engineering Standards SAES-B-068 SAES-J-003

Electrical Area Classification Basic Design Criteria

Saudi Aramco Library Drawings (Non-Mandatory)

DC-950040 Instrument Piping Details Pressure Indicators &

Switches - Locally Mounted

Page 2 of 6

Document Responsibility: Instrumentation Issue Date: 8 October 2008

Next Planned Update: 18 May 2013

SAES-J-200

Pressure

DC-950041 Instrument Piping Details Pressure Indicators &

Switches - Panel or Wall Mounted DC-950042 DD-950053

Instrument Piping Details Pressure Instruments - Blind & Indicating Type Field Mounting Details for Instruments

Saudi Aramco Instrument Specification Sheets (ISS) 2773-ENG 8020-212-ENG 8020-213-ENG

3.2

ISS - Pressure Instruments

ISS - Pressure and Differential Pressure Gauges ISS - Pressure and D/P Switches

Industry Codes and Standards

International Electrotechnical Commission IEC 60529

Degree of Protection Provided by Enclosures (IP Code)

National Electrical Manufacturers Association NEMA 250

Process Industry Practices PCCPR001 PCIDP000 PCIDP100 PCIPR000 PCIPR100

4

Pressure Measurement Design Criteria Differential Pressure Installation Details Differential Pressure Transmitter Installation Details Pressure Installation Details

Pressure Transmitter Installation Details Enclosures for Electrical Equipment (1000 Volts Maximum)

Modifications to PIP PCCPR001, Pressure Measurement Design Criteria The following paragraph numbers refer to PIP PCCPR001 (April 2007), which is a part of this standard. The text in each paragraph is an addition, exception, modification, or deletion to the requirements of PIP PCCPR001 as noted. Paragraph numbers not appearing in PIP PCCPR001 are new paragraphs to be inserted. 2.2 3

(Modification Exception) Delete all references to ISA specification forms and replace with reference to Saudi Aramco Instrument Specification Sheets. (Delete complete paragraph)

Page 3 of 6

Document Responsibility: Instrumentation Issue Date: 8 October 2008

Next Planned Update: 18 May 2013

SAES-J-200

Pressure

4.1.1.3

(Modification Exception) Delete all references to ISA specification forms. The minimum data set shall be in accordance with Saudi Aramco Instrument Specification Sheets.

(Additional Paragraph) All instruments and their accessories shall meet the relevant requirements of SAES-J-003 pertaining to ambient conditions. Locally mounted instruments and their accessories shall meet the relevant electrical area classification requirements of SAES-B-068. (Addition) Add the word \"Process\" before the word \"pressure\".

(Modification Exception) Pressure gauges shall have safety glass. Plastic lenses (acrylic or polycarbonate) can only be used if they are the standard window material for gauges supplied as part of a package unit. Lenses, when used, are to be compatible with the surrounding process and ambient environments.

(Addition) Add the following sentence at the end of the paragraph: \"siphons shall also be used for process fluids with a temperature over 250°C (480°F) when the gauge is above the tap connection.\"

(Additional Paragraph) Standard ranges shall be selected such that the normal operating pressure falls between 30% and 70% of the scale range. (Additional Paragraph) Gauges supplied by vendors as part of other

pneumatic devices such as current to pneumatic converters, instrument air supply regulators, valve positioners, piston actuators, and similar devices shall be vendor standard unless otherwise specified.

(Additional Paragraph) Switch Process side connections shall be ½ inch NPT. Connections for pneumatic tubing shall be ¼ inch NPT female, minimum. Electrical conduit connections shall be ½ inch or ¾ inch NPT. (Additional Paragraph) Electric switch contacts shall be snap acting, single-pole, double-throw (SPDT) as a minimum. The contact rating shall be sufficient to operate solenoids, relays, or other devices as specified in the data sheet without the need for additional or interposing relays. Hermetically sealed switch contacts are preferable.

(Additional Paragraph) Switch actuation, as the result of increasing or decreasing pressure must be specified.

(Additional Paragraph) Pressure transmitters shall be Smart.

(Additional Paragraph) Differential pressure transmitters shall be Smart.

4.1.12

4.2.2 4.2.3

4.2.7

4.2.8 4.2.9

4.3.5

4.3.6

4.3.7 4.4.6 4.5.3

Page 4 of 6

Document Responsibility: Instrumentation Issue Date: 8 October 2008

Next Planned Update: 18 May 2013

SAES-J-200

Pressure

4.6 (New Paragraph) Recorders

Direct-connected, field-mounted recorders shall have a 300 mm diameter chart, and a 24 hour or 7 day chart drive. Only recorder pens with felt tip, or capillary inking systems are acceptable.

4.7 4.7.1 4.7.2

(New Paragraph) Accessories

All pulsation dampeners (or snubbers), siphons, diaphragm seals and similar accessories shall be shown on P&IDs.

Snubber design shall allow easy disassembly to facilitate cleaning. Snubbers shall not be used on switches in critical (e.g., ESD) service. Pulsation dampeners using a restriction orifice or a moving piston are acceptable. Capillary tube-type snubbers are not acceptable.

Gauge savers protecting instruments against pressures that are very high compared to the operating range may be used, except on switches in critical (e.g., ESD) service.

(New Section) Installation Requirements

Branch connection up to and including the first block (root) valve shall meet the applicable Saudi Aramco piping codes. If more than one instrument are sharing a common root valve, means to isolate each instrument independently shall be provided.

Commentary Note:

The device manifold is acceptable to provide the required isolation at the end-use device in clean/non-plugging services when multiple devices share a common root valve connection.

4.7.3

5 5.1

5.2 5.3 5.4 5.5

Process connections for direct-mounted instruments shall be located where line vibration is negligible.

For low-pressure service, e.g., furnace draft, the instrument is to be mounted at the same elevation or above the pressure tap.

All pressure instrument installations shall be equipped with vent/drain valves. For additional details of typical pressure instrument installations refer to the referenced Saudi Aramco Library Drawings and PIP PCIPR000, PCIDP000, PCIPR100, and PCIDP100.

Local recorder enclosures shall be NEMA Type 3 or IEC IP 44 as a minimum. Pressure and D/P switch enclosures for indoor use shall be

Page 5 of 6

5.6

Document Responsibility: Instrumentation Issue Date: 8 October 2008

Next Planned Update: 18 May 2013

SAES-J-200

Pressure

NEMA Type 1 or IEC IP 22. For outdoor installation NEMA Type 4 or IEC IP 65 enclosures are required as a minimum.

Revision Summary 18 May 2008 Revised the \"Next Planned Update\". Reaffirmed the contents of the document and reissued

with minor changes.

8 October 2008 Editorial revisions to update the committee membership.

Page 6 of 6